Influence of Floor Air Supply Methods and Impact of Geometric Parameters on the Thermal Performance of Data Centers

The indoor thermal environment of data centers is based on the supply airflow distribution, which is significantly affected by the geometric configuration of the air-supply system.This study compares four commonly used air supply layouts, namely the cold/hot-aisle airflow open-ended system, hot aisle containment system, cold aisle under racks system, and cold aisle containment system.For each air supply layout, geometric Medium Weight factors such as the plenum height, perforation rate, baffle position, and baffle angles were investigated.Using ANSYS Fluent, up to 288 models of CRAC with different air supply modes and configurations were built.

The models were validated using the temperature measurement data at the SmartAisle? cold aisle containment system.The average rack and hot spot temperatures, thermal performance evaluation index, and return temperature index were used as the metrics for comparison.The results show that both increasing the plenum height and decreasing the perforation rate within a certain range contribute Soft Gel to thermal performance improvement.Considering the room temperature profile and evaluation metrics, the overall best performance is achieved in the cold aisle containment case.

Finally, the effects of various factors when using /-shaped and /-shaped baffles were compared using the models of the cold aisle containment system.The results show that when using /-shaped and /-shaped baffles, the optimal perforation rate is 20%, while the optimal static pressure height is 0.5 m and 0.6 m, respectively.

Overall, /-shaped baffles achieve better temperature uniformity than /-shaped baffles.

Leave a Reply

Your email address will not be published. Required fields are marked *